high voltage proximity tester(HVP-275) Produkte ID: HVP-275

HVP-275 Features

‧ Sealed by "" O"" Ring.
‧ 8 voltage settings: 240Vac, 2kV, 6kV, 11kV, 22kV, 33kV,
132kV, and 275kV
‧ High bright LEDs visual indication
‧ Sound indication
‧ Easy-to-proov method
‧ Self-test selection
‧ Use 3 x 1.5V “C” batteries
‧ High impact nylon casing
‧ Non-contact work by proximity
‧ Compatible with most link sticks
‧ Light weight, robust, & compact
‧ Suitable for indoor and outdoor use
‧ Detect low voltage on any systems
‧ Easy access to batteries
‧ No special parts needed
‧ Three-year warranty
‧ Simple and efficient to use

Kategorie: Elektrische Tester
Zertifikat:CE
  • Introduction:
    • The TECPEL HVP-275 is a high voltage proximity detector.
    • It has eight voltage detection settings from 240Vac to
    • 275kVac. The HVP-275 consists of an internal pickup
    • sensor plate, a sensitivity selector, a visual and a
    • sound annunciator. With the HVP-275, physical contact
    • with electrical conductors is not necessary when
    • testing for live lines. This tester works by proximity.
    • Its sensor senses the radiated field which surrounds
    • live conductors. Radiated field strength increases
    • with voltage and decreases quickly with distance or
    • earth shielding. The radiated field from a cable of
    • closely bunched conductors supplied by three phase
    • power tends to cancel (See “Limitations of use”
    • paragraph). Detecting distance of a 250Vac single
    • live wire is approximately 10cm. With a bunched
    • neutral and earth cable, as in a flexible cable, the
    • distance is reduced to 5cm.
    • Some of the typical uses are : identify and check live
    • cables; find fault in flexible cables; check earth
    • equipment; service neon lightning; trace live wires;
    • check high frequency radiation; detect residual or
    • induced voltages. For example, faults in damaged
    • flexible cables are found by applying low voltage to
    • each conductor. Earthing the remainder and moving
    • the tester along the cable until the change in condition
    • is obtained. (Flexible cables which are used in mining
    • and building industries, are readily repairable when
    • the break in the cable is located.)
    • When testing for high voltage, the rotary switch
    • (attenuator) is used to identify and differentiate
    • various HV live cables. The tester must be used in
    • conjunction with a long and insulating rod when
    • measuring high voltage (kV). However, the HVP-275 is
    • a non-contact tester and it is advised that the tester
    • should never come into contact with cables (kV) as
    • this tester is merely a non-contact AC proximity tester.
    • Checking or proofing the tester is easy. Switch the
    • sensitivity to 240V and place the dome against a low
    • voltage live conductor or rub the dome with a cloth or
    • against an item of clothing as this generates a static
    • DC which triggers the detection of circuit. The light
    • and beeper should go “on” as if a live wire is being approached. Approaching the dome near a computer screen or a TV screen should also trigger
    • the tester while on the 240V selection. The power consumption of the 275HP is very low, and the
    • tester should always be tested as described above before using it.
  • Specifications:
    • Expected test results ( laboratory testing ) :
    • Range
    • 240V
    • 2kV
    • 6kV
    • 11kV
    • 22kV
    • 33kV
    • 132kV
    • 275kV
    • Typical observation of test results made in the field :
    • Range
    • 11kV
    • 22kV
    • 33kV
    • 132kV
    • 275kV
    • Operated from
    • Variable from 80V
    • or depending on the type of source
    • 250V
    • 500V
    • 1000V
    • 1500V
    • 4000V
    • 8000V
    • 22kV
    • Min. Detection MDV as % of
    • Voltage (MDV) Line Voltage
    • 1kV 9.1%
    • 2kV 9.1%
    • 3.1kV 9.4%
    • 12.5kV 9.5%
    • 22.5kV 8.2%
  • Limitation of usage.
    • Limitations of use :
    • It is recommended that the 275HP is not used in HV yards of mixed voltages.
    • In the presence of mixed voltages, the tester can become unreliable.
    • Problems can arise when the tertiary circuit of a 275/133/11kV transformer is
    • tested. The electric field of the HV and MV bus bars can trigger the detector when
    • it is about 3m above the ground. This is common with most of the electric field
    • voltage detectors, and the users should be aware of it. The tester can pick up
    • adjacent circuit to the one being tested and indicate the wrong information to the
    • user. Limitations of use :
    • It is recommended that the 275HP is not used in HV yards of mixed voltages.
    • In the presence of mixed voltages, the tester can become unreliable.
    • Problems can arise when the tertiary circuit of a 275/133/11kV transformer is
    • tested. The electric field of the HV and MV bus bars can trigger the detector when
    • it is about 3m above the ground. This is common with most of the electric field
    • voltage detectors, and the users should be aware of it. The tester can pick up
    • adjacent circuit to the one being tested and indicate the wrong information to the
    • user.


 

Q&A:

We already bought 20 set of HVP-275 form you. We sold to customer and they found there is no range for 69 and 115 kV. In case of they want to use it with 69 kV & 115 kV, is it work? If it can be used, what range they should select between 33 and 132 kV ?

If the customer sold HVP-275 already. They can select the range of 33 kV to detect 69 kV and 115 kV, it's ok to do that.The range of 33 kV can detect voltages that's greater than 33 kV. It's not only for the voltage 33 kV.You can identify the strength of the voltages according to the distance. The higher the voltage, the longer the detection distance. This is a HV proximity detector